5.3 Motor/Characterisitic Curve Parameters
BU 0200 GB
Subject to technical alterations
101
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P217 Oscillation
damping
S
P
0 ... 400 %
[ 10 ]
With the oscillation damping, idling current harmonics can be damped. Parameter 217 is a
measure of the damping power.
For oscillation damping the oscillation component is filtered out of the torque current by means
of a high pass filter. This is amplified by P217, inverted and switched to the output frequency.
The limit for the value switched is also proportional to P217. The time constant for the high pass
filter depends on P213. For higher values of P213 the time constant is lower.
With a set value of 10% for P217, a maximum of ± 0.045Hz are switched in. At 400% in P217,
this corresponds to ± 1.8Hz
The function is not active in “Servo mode, P300”.
P218 Modulation
depth
S
50 ... 110 %
[ 100 ]
This setting influences the maximum possible output voltage of the FI in relation to the mains
voltage. Values <100% reduce the voltage to values below that of the mains voltage if this is
required for motors. Values >100% increase the output voltage to the motor increased the
harmonics in the current, which may cause oscillation in some motors.
Normally, 100% should be set.
P219
Automatic flux adjustment
S
25 ... 100 % / 101
[ 100 ]
With this parameter, an automatic adjustment of the magnetic flux to the motor load can be
made. P219 is a limiting value, to which the field in the motor can be reduced.
As standard, the value is set to 100%, and therefore no reduction is possible. As minimum, 25%
can be set.
The reduction of the field is performed with a time constant of approx. 7.5 sec. On increase of
load the field is built up again with a time constant of approx. 300 ms. The reduction of the field
is carried out so that the magnetisation current and the torque current are approximately equal,
so that the motor is operated with “optimum efficiency”. An increase of the field above the
setpoint value is not intended.
This function is intended for applications in which the required torque only changes slowly (e.g.
pumps and fans). Its effect therefore replaces a quadratic curve, as it adapts the voltage to the
load.
NOTE:
This must not be used for lifting or applications where a more rapid build-up of the
torque is required, as otherwise there would be overcurrent switch-offs or inversion
of the motor on sudden changes of load, because the missing field would need to
be compensated by a disproportionate torque current.
101 = automatic,
with the setting P219=101 an automatic magnetisation current controller is
activated. The ISD controller then operates with a subordinate magnetizing controller,
which improves the slippage calculation, especially at higher loads. The control times
are considerably faster compared to the Normal ISD control (P219 = 100)