3.2 External Control Unit
BU 0200 GB
Subject to technical alterations
47
Parameterisation with the SimpleBox
The
parameterisation
of the FI can be performed in various operating states. All parameters can always be
changed online. Switching to the parameter mode occurs in different ways depending upon the operating
states and the enabling source.
1. If there is no enable (if necessary, press the STOP key
) it is possible to switch to the
parameterisation mode directly from the operating value display with the value keys
or
.
P 0 _ _
/
P 7 _ _
2. If an enable is present via the control terminals or a serial interface and the frequency inverter is
produces an output frequency, it is also possible to switch to the parameterisation mode directly
from the operating value display using the value keys
.
P 0 _ _
/
P 7 _ _
3. If the FI has been enabled via the SimpleBox (START key
), the parameterisation mode can be
accessed by pressing the START and ENTER keys (
+
OK
) simultaneously.
4. Switching back to the control mode is achieved by pressing the START key
.
Return to operating value
display
Save currently changed
parameter value
One level back each time
until the operating value
display is reached
Next menu group or
parameter value
Exit setting without saving
Previous menu group or
parameter value
Switchover from parame-
terisation to control
Parameter set display
Switch from control
to parameterisation
Changing parameter values
To access the parameter section, one of the value keys,
or
must be pressed. The display changes to
the menu group display
P 0 _ _
...
P 7 _ _
. After pressing the OK key
OK
access to the menu group is
obtained and the required parameter can be selected with the value keys.
All parameters are arranged in order in the individual menu groups in a continuous scroll pattern. It is
therefore possible to scroll forwards and backwards within this section.
Each parameter has a parameter number
P
x x x
. The significance and description of the parameters
starts in Section 5 "Parameterisation"
NOTE:
Some parameters (e.g. P502) have additional levels (Arrays) , in which further settings can be
made, e.g.:
P 0 1
P5 0 2
P 0 2
o f f
o f f
Settin g:
Value o f m aster fun ction 1
Settin g:
Value o f m aster fun ction 2
EN TER
ENTER
ENTER
VA LU E