5.5 Control Terminals
BU 0200 GB
Subject to technical alterations
109
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P402
[-
01]
...
[-
02]
Analog input adjustment 1: 0%
S
-50.00 ... 50.00 V
[ 0.00 ]
[-01] =
External analog input 1
[-02] =
External analog input 2
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the minimum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
equivalent to the setpoint set via P104 >Minimum frequency<.
Typical setpoints and corresponding settings:
0 – 10 V
0.00
V
2 – 10 V
2.00 V (for function 0-10 V monitored)
0 – 20 mA
0.00 V (internal resistance approx. 250
)
4 – 20 mA
1.00 V (internal resistance approx. 250
)
P403
[-
01]
...
[-
02]
Analog input adjustment 1: 100%
S
-50.00 ... 50.00 V
[ 10.00 ]
[-01] =
External analog input 1
[-02] =
External analog input 2
... only with
SK CU4-IOE or
SK TU4-IOE
This parameter sets the voltage which should correspond with the maximum value of the
selected function for the analog input 1 or 2. In the factory setting (setpoint) this value is
corresponds with the setpoint set via P105 >Maximum frequency<.
Typical setpoints and corresponding settings:
0 – 10 V
10.00
V
2 – 10 V
10.00 V (for function 0-10 V monitored)
0 – 20 mA
5.00 V (internal resistance approx. 250
)
4 – 20 mA
5.00 V (internal resistance approx. 250
)
P400 ... P403
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
P402 P403
Setpoint
voltage
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
negative
P402
P403
Setpoint
voltage