Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P546
[-
01]
...
[-
03]
Function Bus setpoint 1… 3
S
P
0 ... 24
[ -01 = 1 ]
[ -02 = 0 ]
[ -03 = 0 ]
In this parameter, a function is allocated to the output setpoint during bus actuation.
NOTE:
Further details can be found in the Bus Manual BU 0250 or in the description of
P400.
[-01] = Bus setpoint value 1
[-02] = Bus setpoint value 2 (only for PPO type 2 or 4)
[-03] = Bus setpoint value 3 (only for PPO type 2 or 4)
Possible setting values:
0 =
Off
1 =
Setpoint frequency (16 Bit)
2 =
Frequency addition
3 =
Frequency subtraction
4 =
minimum frequency
5 =
Maximum frequency
6 =
PI process controller actual value
7 =
PI process controller setpoint
8 =
Actual frequency PID
9 =
Actual PID frequency limited
10 =
Actual PID frequency monitored
11 =
Limiting torque current
12 =
Torque current switch-off limit
13 =
Limiting current
14 =
Current switch-off limit
15 =
Ramp time
16 =
Lead torque (P214) multiplication
17 =
Servo mode torque
18 =
Curve travel calculator
19 =
Digital In Bits 0...7
20 =
...24 Reserved for Posicon
P549 PotentiometerBox
function
S
0 ... 3
[ 1 ]
This parameter provides the possibility of adding a correction value (fixed frequency, analog,
bus) to the current setpoint value by means of the SimpleBox/ParameterBox keyboard.
The adjustment range is determined by the auxiliary setpoint value P410/411.
0 =
Off
1 =
Not applicable
2 =
Frequency addition
3 =
Frequency subtraction