5.8 Information
BU 0200 GB
Subject to technical alterations
135
Parameter
Setting value / Description / Note
Device
Supervisor
Paramter-
satz
P705
... - 01
...
... - 05
VDC previous fault 1...5
S
0 ... 1000 V DC
This parameter stores the link voltage that was being delivered at the time the error occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P706
... - 01
...
... - 05
Parameter set previous fault 1...5
S
0 ... 3
This parameter stores the parameter set code that was active when the error occurred. Data for
the previous 5 faults are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P707
... - 01
...
... - 03
Software version/ revision
0.0 ... 9999.9
This parameter shows the software and
revision numbers in the FI. This can be
significant when different FIs are
assigned the same settings.
Array 03 provides information about any
special versions of the hardware or
software A zero stands for the standard
version.
... - 01 =
Version number (1.0)
... - 02 =
Revision number (R1)
... - 03 =
Special version of hardware/software (0.0)
P708
Status of digital inputs
00000 ... 11111
(binary)
or
00 ... 1F
(hexadecimal)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
Bit 0 =
Digital input 1
Bit 1 =
Digital input 2
Bit 2
=
Digital input 3
Bit 3 =
Digital input 4
Bit 4 =
PTC input
Bit 4
Bits 3 -0
Minimum value
0
0
0000
0
Binary
hex
Maximum value
1
1
1111
F
Binary
hex
SimpleBox:
The binary Bits are converted into a hexadecimal value and displayed.
ParameterBox:
The Bits are displayed increasing from right to left (binary).