NORDAC SK 200E Handbuch
134
Subject to technical alterations BU
0200
GB
5.8 Information
Parameter
Setting value / Description / Note
Device
Supervisor
Paramter-
satz
P700 Actual
error
0.0 ... 21.4
Actual fault present. Further Details in Chapter 6 Error messages.
SimpleBox:
Descriptions of the individual error numbers can be found in the point Error
messages.
ParameterBox:
Errors are displayed in plain text, further information can be found in the point
Error messages.
P701
... - 01
...
... - 05
Last fault 1...5
0.0 ... 21.4
This parameter stores the last 5 faults. Further details in Chapter 6, Error messages.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P702
... - 01
...
... - 05
Freq. previous fault 1...5
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P703
... - 01
...
... - 05
Current previous fault 1...5
S
0.0 ... 999.9 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P704
... - 01
...
... - 05
Voltage previous fault 1...5
S
0 ... 600 V AC
This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.