5.6 Additional Parameters
BU 0200 GB
Subject to technical alterations
121
5.6 Additional parameters
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P502
... - 01
...
... - 03
Master function value
S
P
0 ... 21
[ -01 = 0 ]
[ -02 = 0 ]
[ -03 = 0 ]
Selection of up to 3 master values:
[-01] = Master value 1
[-02] = Master value 2
[-03] = Master value 3
Selection of possible setting values for master values:
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current
5 =
Status of digital inputs and outputs
6 =
... 7 reserved
8 =
Desired frequency
9 =
Error message
10 =
... 11 reserved
12 =
Digital Out Bit 0…7
13 =
... 16 reserved
17 =
Value analog input 1
18 =
Value analog input 2
19 =
Desired frequency master value
20 =
Desired frequency after master value ramp
21 =
Actual frequency without master value slip
P503
Master function output
S
0 ... 1
[ 0 ]
The output of the master function via the system bus is activated with this parameter.
The control words and setpoint values to be output refer to the P509 source of the FI control.
The master value to be transmitted via the system bus is determined by parameter P502.
0 =
Off
1 =
System bus
P504 Pulse
frequency
S
3.0 ... 16.0 kHz
[ 6.0 ]
The internal pulse frequency for actuating the power component can be changed with this
parameter. A higher setting reduces motor noise, but leads to increased EMC emissions and
reduction of the possible motor nominal torque.
NOTE:
The radio interference suppression limiting curve A1 according to EN55011 is
complied with at a setting of 6.0kHz on condition that the wiring guidelines are
complied with. For further details, see Section 8.4. EMC limit value classes.
NOTE:
Raising the pulse frequency leads to a reduction of the possible output current,
depending on the time (I
2
t curve). For further details, see Section 8.5. Power de-
rating.