NORDAC SK 200E Handbuch
154
Subject to technical alterations BU
0200
GB
Anzeige in der
SimpleBox
Error
text in the Parameter Box
Cause
Remedy
Group
Detail in
P700 / P701
E005
5.0 Overvoltage
link
voltage
Frequency inverter link circuit voltage is too high
Reduce energy return by means of a braking resistance
Extend braking time (P103)
If necessary, set switch-off mode (P108) with delay (not for
lifting equipment)
Extend emergency stop time (P426)
5.1 Overvoltage
mains
Mains voltage is too high
Please check 380V-20% ... 480V+10%
or 200 ... 240V
10%
E006
6.0 Link
voltage
undervoltage
(charging error)
FI mains / link voltage too low
Check mains voltage 380V-20% ... 480V+10%
or 200 ... 240V
10%
6.1 Mains
undervoltage
E008
8.0
EEPROM parameter loss
(maximum value exceeded
Error in EEPROM data
Software version of the stored data set not compatible with
the software version of the FI.
NOTE:
Faulty
parameters
are automatically reloaded
(factory setting).
EMC interferences (see also E020)
8.1
Invalid inverter type
EEPROM faulty
8.2 --
--
8.3 Customer
interface
incorrectly identified
(customer’s interface
equipment)
The upgrade level of the frequency inverter was not
correctly identified.
Switch mains voltage off and on again.
8.4 Database
version
incorrect
8.7
Original and mirror not
identical
E009
--- SimpleBox
error
SPI Bus faulty, no communication with the SimpleBox.
Check correct connection of SimpleBox.
Switch mains voltage off and on again.