6 Error Messages
BU 0200 GB
Subject to technical alterations
153
6.2 Table of possible error messages
Anzeige in der
SimpleBox
Error
text in the Parameter Box
Cause
Remedy
Group
Detail in
P700 / P701
E001
1.0
FI overtemperature (heat
sink)
Error signal from output stage module (static)
Reduce ambient temperature <50°C (see also Section 7,
technical details).
Check control cabinet ventilation
Increase ambient temperature, >25
℃
1.1
FI overtemperature (interior)
E002
2.0
Overtemperature, motor
(from PTC)
Motor temperature sensor has triggered
Reduce motor load
Increase motor speed
Use motor external fan
2.1 Overtemperature,
motor
(from
I²t monitoring)
Only if I
2
t - Motor (P535) is
programmed.
I
2
t- Motor has triggered
Reduce motor load
Increase motor speed
2.2
Overtemperature from digital
input
P420=13
Temperature monitor has triggered
Digital input is low
E003
3.0
Converter overcurrent (I
2
t)
I
2
t limit has triggered, e.g. > 1.5 x I
n
for 60s (please also
note P504)
Continuous overload at inverter output
3.1
Chopper overcurrent (U
2
t)
U
2
t limit for brake chopper has triggered
(please also see P554, P555, P556, P557)
Avoid overcurrent in braking resistance
3.2
Overcurrent IGBT monitoring
125%
De-rating (power reduction)
125% overcurrent for 50ms
Brake chopper current too high
for fan drives: enable flying start circuit
(P520)
See also
Section 8.5
3.3
Overcurrent IGBT monitoring
150%
De-rating (power reduction)
150% overcurrent
Brake chopper current too high
E004
4.0 Overcurrent
module
Error signal from module (short duration)
Short-circuit or earthing fault at FI output
Motor cable is too long
Use external output choke
brake resistor faulty or resistance too low (Section 7)
4.1
Overcurrent pulse switch-off
P537 (pulse current switch-off) was reached 3x within 50ms
(only possible if P112 and P536 are disabled)
FI is overloaded
Check motor data (P201 … P209)