3.4 External Technology Unit
BU 0200 GB
Subject to technical alterations
79
3.5.6
PotentiometerBox, SK TU4-POT-...
Data:
Supply according to version
1~
110-240V
=
SK TU4-24V-123-B
1~
380-480V
=
SK TU4-24V-140-B
24V = Output voltage
Button - ON R / OFF / ON L
Setpoint potentiometer - 0…100%
v/f converter
With appropriate wiring, the frequency inverter can be
controlled directly using the PotentiometerBox. No
additional internal or external components are required.
The motor can be started, stopped and the direction of rotation changed by means of the buttons. The LEDs
indicate the status of the box buttons.
The required setpoint value of the frequency is adjusted with the potentiometer after it has been enabled
(green button).
The integrated 24V mains unit can supply a control voltage to the SK 200E and any additional modules.
Connection diagram, example:
Frequency inverter
SK 205E-.../ SK 215E-...
Contro
l termin
al bar
44
40
.
.
21
22
23
24
.
L1 - L2/N - L3
115/230/400V
PotentiometerBox
SK TU4-POT-...
+ SK TI4-TU-NET
L1 - L2/N
115/230/400V
24V=
GND
R
L
0-100%
1/3~
115/230/400V
+
PE
Control terminal bar
43 40 43 ... B1 B2 B3
Poti
0-10
0
L
R
DIP switch setting:
DIP3 = off, DIP4 = on, DIP5 = off
(With this, no further parameter settings are necessary!)
or
Recommended
parameter setting, DIP1-8 = off:
P400 [07] = 1 P420 [02] = 2
P420 [01] = 1 P420 [03] = 26