NORDAC SK 200E Handbuch
136
Subject to technical alterations BU
0200
GB
Parameter
Setting value / Description / Note
Device
Supervisor
Paramter-
satz
P709
... - 01
...
... - 07
Analog input values
-100.0 ... 100.0 %
Displays the measured analog input value.
[-01] =
Potentiometer 1
, internal FI potentiometer P1 (Section 4.1.3), for the adjustment
of “maximum frequency”, “minimum frequency” and “ramp time”
[-02] =
Potentiometer 2
, internal FI potentiometer P2 (Section 4.1.3) with fixed steps, the
function can also be entered via the DIP switch.
[-03] =
External analog input 1
, of I/O extension SK CU4-/TU4-IOE.
[-04] =
External analog input 2
, of I/O extension SK CU4-/TU4-IOE.
[-05] =
Setpoint module
, in preparation
[-06] =
Digital input 2
, analog function of FI digital input 2
[-07] =
Digital input 3
, analog function of FI digital input 3
P710
Voltage analog output
0.0 ... 10.0 V
Displays the delivered value of analog output.
P711 Output
status
00 ... 11 (bin)
or
0 ... 3 (hex)
Displays the actual status of the digital outputs.
Bit 0 =
Digital output 1
Bit 1 =
Mechanical brake
P714 Operating
time
0.00 ... ___ h
This parameter shows the time for which the FI was connected to the mains and was ready for
operation.
P715 Run
time
0.00 ... ___ h
This parameter shows the time for which the FI was enabled and supplied current to the output.
P716 Actual
frequency
-400.0 ... 400.0 Hz
Displays the actual output frequency.
P717
Actual rotation speed
-9999 ... 9999 rpm
Displays the actual motor speed calculated by the FI.
P718
... - 01
... - 02
... - 03
Actual setpoint frequency
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint.
... -01
= Actual setpoint frequency from the setpoint source
... -02
= Actual setpoint frequency after processing in the FI status machine
... -03 =
Actual setpoint frequency after the frequency ramp
P719 Actual
current
0.0 ... 999.9 A
Displays the actual output current.