5.4 Control Parameters
BU 0200 GB
Subject to technical alterations
105
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter set
P312
Torque current controller P
S P
0 ... 800 %
[ 200 ]
Current controller for the torque current. The higher the current controller parameters are set,
the more precisely the current setpoint is maintained. Excessively high values in P312 generally
lead to high-frequency oscillations at low speeds; on the other hand, excessively high values in
P313 generally produce low frequency oscillations across the whole speed range.
If the value "Zero" is entered in P312 and P313, then the torque current control is switched off.
In this case, only the motor model precontrol is used.
P313
Torque current controller I
S P
0 ... 800 % / ms
[ 125 ]
I-component of the torque current controller. (See also P312 >Torque current controller P<)
P314
Torque current controller limit
S P
0 ... 400 V
[ 400 ]
Determines the maximum voltage increase of the torque current controller. The higher the
value, the greater the maximum effect that can be exercised by the torque current controller.
Excessive values in P314 can specifically lead to instability during transition to the field
weakening zone (see P320). The values for P314 and P317 should always be set roughly the
same, so that the field and torque current controllers are balanced.
P315
Field current controller P
S P
0 ... 800 %
[ 200 ]
Current controller for the field current. The higher the current controller parameters are set, the
more precisely the current setpoint is maintained. Excessively high values for P315 generally
lead to high frequency vibrations at low speeds. On the other hand, excessively high values in
P316 generally produce low frequency vibrations across the whole speed range If the value
"Zero" is entered in P315 and P316, then the field current controller is switched off. In this case,
only the motor model precontrol is used.
P316
Field current controller I
S P
0 ... 800 % / ms
[ 125 ]
I-component of the field current controller. See also P315 >Field current controller P<
P317
Field current controller limit
S P
0 ... 400 V
[ 400 ]
Determines the maximum voltage increase of the torque current controller. The higher the
value, the greater is the maximum effect that can be exercised by the field current controller.
Excessive values in P317 can specifically lead to instability during transition to the field
reduction range (see P320). The values for P314 and P317 should always be set roughly the
same, so that the field and torque current controllers are balanced.
P318
Field weakening controller P
S P
0 ... 800 %
[ 150 ]
The field weakening controller reduces the field setpoint when the synchronous speed is
exceeded. Generally, the field weakening controller has no function; for this reason, the field
weakening controller only needs to be set if speeds are set above the nominal motor speed.
Excessive values for P318 / P319 will lead to controller oscillations. The field is not weakened
sufficiently if the values are too small or during dynamic acceleration and/or delay times. The
downstream current controller can no longer read the current setpoint.
P319
Field weakening controller I
S P
0 ... 800 % / ms
[ 20 ]
Affects only the field weakening range, see P318 >Field weakening controller P<