5.6 Additional Parameters
BU 0200 GB
Subject to technical alterations
129
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P542
Set analog output
S
0.0 ... 10.0 V
[ 0.0 ]
The analog output of the FI can be set with this function, independently of the actual operating state.
To do this, the relevant analog output must be set to the function "External control" (P418 = 7).
This function can either be used manually or in combination with a bus control. The value set
here will, once confirmed, be produced at the analog output.
... only with
SK CU4-IOE or
SK TU4-IOE
P543
[-
01]
...
[-
03]
Actual bus value 1… 3
S
P
0 ... 22
[ -01 = 1 ]
[ -02 = 4 ]
[ -03 = 9 ]
In this parameter the return value on bus actuation can be selected.
NOTE:
Further details can be found in the respective Bus Manual BU 0250 or in the
description of P418.
[-01] = Actual bus value 1
[-02] = Actual bus value 2 (only for PPO type 2 or 4)
[-03] = Actual bus value 3 (only for PPO type 2 or 4)
Possible setting values:
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current (100% = P112)
5 =
State of digital inputs and outputs
2
6 =
... 7 reserved
8 =
Desired frequency
9 =
Error number
10 =
... 11 reserved
12 =
Bus IO Out Bits 0...7
13 =
... 16 reserved
17 =
Value analog input 1 (P400)
18 =
Value analog input 2 (P405)
19 =
Desired frequency master value (P503)
20 =
Desired frequency after master value ramp
21 =
Actual frequency without master value slip
22 =
Speed of rotation from encoder
2
The assignment of the dig. inputs in PP543 = 5
Bit 0 = DigIn 1
Bit 1 = DigIn 2
Bit 2 = DigIn 3
Bit 3 = DigIn 4
Bit 4 = DigIn 5
Bit 5 = DigIn 6
Bit 6 = DigIn 7
Bit 7 = reserved
Bit 8 = reserved
Bit 9 = reserved
Bit 10 = reserved
Bit 11 = reserved
Bit 12 = Out 1
Bit 13 = Out 2
Bit 14 = Out 3
Bit 15 = Out 4