89
5
Settings
5. Settings
Digitax SF
Instruction Manual
5. Parameters
5.
Parameters
No. 644.0
Internal position:
Point table - Point number output method
Settings
Default
Characteristics
0 to 2
1
Function
Use
Select the output timing for a point number (PM1...3) when using I/O assignment
Option1 for Positioner Drive.
Settings
Output timing for Motion Start Point Number
0
Upon motion start
1
Upon motion complete
2
Upon motion start of each point
Prerequisite
The following two settings are necessary.
・Control Mode (2.0) = 0 (Position Control Mode)
・Command Mode (3.0) = 3 (Internal command mode/Option I/O Setting)
No. 645.0
Homing:
Home reference signal selection
Settings
Default
Characteristics
0 to 2
2
Function
Use
Select the signal that the home position will be referenced to.
Settings
Reference Signal 1
0
Any user sp
e
cified position
1
Stopper
2
Home-
sensor
-front-end
(*)
*) Starting point is located on the
sensor
Regardless of the
Re-detection of Home position
sensor
(645.3) setting, this setting indicates a motion of at first
moving backward to a position where homing can be performed.
Sensor
Position
Origin
Homing Speed
Speed
Homing Cre
e
p Speed
No. 645.1
Homing:
Encoder Z-phase selection
Settings
Default
Characteristics
0, 1
1
Function
Use
To add encoder Z-phase as the reference position after the Home Reference Signal
is detected, set this parameter to 1.
Settings
Encoder Z-phase
0
Disable
1
Enable
-
-
-
Summary of Contents for Control Techniques Digitax-SF DA21223
Page 6: ...6 MEMO Digitax SF Instruction Manual ...
Page 23: ...17 MEMO Digitax SF Instruction Manual 1 Before Use 2 Overview ...
Page 283: ...48 MEMO Digitax SF Instruction Manual 6 Operation 5 Position Control Mode ...
Page 329: ...46 MEMO Digitax SF Instruction Manual 7 Tuning ...
Page 330: ...8 8 Troubleshooting 2 2 4 5 5 6 8 8 9 17 18 19 20 21 22 23 ...
Page 353: ...24 MEMO 8 Troubleshooting Digitx SF Instruction Manual ...