Installation and programming manual
Compliancy with the regulations in force
93
•
The following options must not be activated in the “Panel Options” section:
•• ReaderBuzzer OFF
•• BypassAlsoTamper
•
In the section “Other parameters - FaultForNotReady”, enable the following options:
•• Zone fuse fault
•• IBUS fuse fault
•• Low battery
•• Mains failure
•• Tel. line down
•• Jamming
•• Low battery WLS
•• WLS zone loss
•• LossTamp.ongoing
•
Zones configured as “24H”, “Automation” are non-compliant.
•
Zones programmed as “Arm”, “Disarm”, “Switch” or “Follow” comply only when
activated by keyswitches with more than 10,000 code combinations.
•
An input is set up for system fault management.
•
You must delete any programming relating to outdoor sounderflashers - from the
respective alarm event in the “Outputs” section - for all zones with the “Fault Zone”
attribute. You can programme indoor sounderflashers via the “Other outputs” option.
•
The telephone dialer must be enabled.
•
The system must include a self-powered sounderflasher for intrusion-alarm event
signaling
•
If you use a digital dialer or voice dialer with SmartLogos30M board for
transmissions, a telephone number must be reserved for the following events:
•• All events generated by zones with the “Hold-up” attribute.
•• All events generated by “Instant”, “Delayed”, “Delayed unhidden” and “Route”
•• All events generated by terminal, peripheral and control panel tamper.
•• All faults detected by the control panel.
•
The “Alarm Cycles” parameter of each zone must be set between 3 and 10.
•
The “Mains fail.Delay” parameter must be set at no more than 1 minute.
•
The “Requires code” option on the function-key shortcuts must be enabled for all the
assigned shortcuts.
•
The “StopTelOn Disarm” partition option must not be enabled.
•
The “Entry Time” of each partition must be set at a maximum of 45 seconds.
•
You must enable the “Priority” option for any alarm events associated with “Hold-up”
zones.
•
“Failed to arm” and “Forced arming” events must be saved to the Events log.
•
The programmed “LowBattery delay” must not be programmed at more than 5
minutes.
EN50131-3, GRADE 3
Adhering to the following instructions guarantees compliance with EN50131-3 Grade 3:
•
In the “Parameters” section, enable option “50131 Grade 3”.
•
If the installation uses detectors with an anti-mask function, each anti-mask signal
must be managed as follows:
•• Prepare an input terminal for the anti-mask signal connection.
•• Programme the following parameters:
-
“Description”: assign an explanatory description to the signal
-
“Fault zone”: enable this option
-
“NoArm IfNotReady”: enable this option
•
Use an ATS4 notification appliance:
•• protocol: SIA-IP with encryption
•• interface: SmartLAN/G or SmartLAN/SI
EN50131-6, GRADE 3
Adhering to the following instructions guarantees compliance with EN50131-6 Grade 3
(Power supplies):
•
Remove the power supply unit (
Table 4: Control panels - description of parts, A
).
•
Install an EN50131-6 Grade 3 certified power supply unit alongside the control panel
enclosure. This power supply unit will provide the following output signals:
•• G1 power system fault (overvoltage, overcurrent, short circuit)
•• G2 mains power failure fault
•• G3 battery fault