Installation and programming manual
Options and programming methods
71
EXAMPLES
If you wish to generate an alarm (i.e. activate sounderflashers and dialer calls) when only two
PIRs (DET1 and DET2) go into alarm status within a pre-set time.
•
T0000; temporizer 1 will activate when the “Zone alarm DET1” Start event activates for 30 seconds
•
T0001; temporizer 2 will activate when the “Zone alarm DET2” Start event activates for 30 seconds
•
Both conditions must occur together (AND)
T0000 AND T0001
•
You must set the activation of the sounderflasher and dialer calls on a similarly-configured
programmable event.
•
If the programmable event activates an on-BUS sounderflasher, associate its deactivation with an
event.
If you wish to activate an output for 40 seconds when key 17 is used to arm partition 1, and to
disarm and the same output when the partition disarms.
•
T0000; associate temporizer 1 with the activation of the Start event of key 17 recognition
•
T0000; temporizer 1 with a 40 second timeout, “temporizer active with delay” option enabled
•
T0000; associate temporizer 1 with the restoral of the reset event of partition 1
•
Programmable event 1 must be programmed as:
T0000
•
Select the output you wish to activate in concurrence with the programmable event
•
If the programmable event activates an on-BUS sounderflasher, associate its deactivation with an
event.
If you wish to receive a telephone call when a zone x, which belongs to partitions 1 and 2, is
violated and one of the two partitions is armed
The automation zone x always generates the zone alarm event (even when the partitions are
disarmed). However, the programmable event will occur only when the zone x is in alarm status
and at least one of the two partitions is armed.
•
Configure zone x as “automation” belonging to partitions 1 and 2
•
Remove all the outputs and phone calls associated with the “Alarm zone x” event
•
The programmable event must be programmed as “Alarm zone x” AND (“Partition 1 armed in away
mode” OR “Partition 2 armed in away mode”):
E0010 AND ( E0790 OR E0791 )
•
Associate the programmable event with the telephone call you wish to receive
If you wish to activate a telephone call after 3 consecutive wrong code entries (with a maximum
of 120 seconds between each entry).
•
C0000; counter 1 will activate on activation of the “False code” Start event, with a count of 3, 120
second autoreset time
•
The programmable event must be programmed as:
C0000
•
Associate the programmable event with the telephone call you wish to receive
If you wish to activate a telephone call and output when at least two detectors out of 5 go into
alarm status.
•
The programmable event must be programmed as (“Alarm zone 1” + “Alarm zone 2” + “Alarm zone
3” + “Alarm zone 4” + “Alarm zone 5”)>=2
( E0000 + E0001 + E0002 + E0003 + E0004 ) >= V0002
•
Associate the programmable event with the telephone call you wish to receive and the output you
wish to activate.
6-12
Timer
This programming section deals with the 10 system Timers.
It is possible to programme two “ON” times and two “OFF” times and up to 15
exceptions for each timer of the week.
A timer can be associated with a:
•
P
artition
- if a partition is associated with a timer which controls automatic-arming
operations (refer to
paragraph 5-4 Activations in the User's Manual)
, it will arm when
the timer switches ON and disarm when the timer switches OFF.
•
C
ode
- if a code is associated with a timer, it will be enabled to operate the system
when the timer switches ON, and disabled when the timer switches OFF.
•
K
ey -
if a key is associated with a timer, it will be enabled to operate the system
when the timer switches ON, and disabled when the timer switches OFF.
In order to associate timers with any of the above-mentioned objects, it is necessary to
access the respective control-panel programming section.
Note
The timers must be enabled/disabled by the user
(refer to paragraph 5-4 Activations in the User's
manual
).
On exiting the programming session (via keypad, computer or modem) all the timers will be
enabled automatically. Therefore, if it will be necessary to disable the timers as required.