64
Options and programming methods
The following table shows the events the control panel recognizes, the number of
events for each type, the trigger and restoral method of each event and the event
category (Pulse).
Table 45:
Event type
Name
Occurs when...
Restores when ...
Number of events
Pulse
events
Zone alarm
A zone generates an alarm
A zone restores
One event for each
zone
no
Terminal tamper
A terminal detects tamper (short-circuit or
wire cutting)
A terminal restores
One event for each ter-
minal
no
Partition alarm
A 24h zone which belongs to the partition
generates an alarm, or a zone which
belongs to the partition generates an
alarm during Away mode.
All the zones belonging to the parti-
tion restore (reset).
One event for each
partition
no
StayPartit.alarm
A zone which belongs to a partition armed
in Stay or Instant mode, generates an
alarm.
All the zones belonging to the parti-
tion restore (reset).
One event for each
partition
no
Partition tamper
A zone which belongs to the partition
detects tamper (short-circuit or wire
cutting).
All the zones belonging to the parti-
tion restore (reset).
One event for each
partition
no
Zone bypass
A zone is inhibited
A zone is enabled (switched On)
One event for each
zone
no
Real-time zone
The electrical status of a zone switches
from standby to alarm
The electrical status of a zone
switches from alarm to standby
One event for each
zone
no
The event is independent of the zone type and the armed/disarmed status of the
partitions.
Partit.not ready
A zone which belongs to the partition is not
in standby status.
All the zones belonging to the parti-
tion are in standby status.
One event for each
partition
no
Away arm request
A request is made to arm the interior and
perimeter zones of the partition
A request is made to disarm the par-
tition
One event for each
partition
Yes
Overtime request
A request is made to arm the partition in
Stay mode (perimeter zones only) or in
Instant mode
A request is made to disarm the par-
tition
One event for each
partition
Yes
Partit.AwayArmed
The partition interior and perimeter zones
have been armed effectively
The partition has been disarmed
effectively
One event for each
partition
no
Partit.StayArmed
armed
The partition has been armed effectively in
Stay or Instant mode
The partition has been disarmed
effectively
One event for each
partition
no
Partition reset
A request is made to reset the partition
One event for each
partition
Yes
Exit time
The partition exit time is running
The partition exit time expires
One event for each
partition
no
Entry time
The partition entry time is running
The partition entry time expires
One event for each
partition
no
Pre-arm time
The partition Pre-arm time is running
The partition Pre-arm time expires
One event for each
partition
no
Overtime request
A request for overtime relating to the
partition is made
One event for each
partition
Yes
Chime
A chime zone belonging to the partition is
violated
One event for each
partition
Yes
Forced arming
At the time of an arming command, relat-
ing to one or more partitions, there are
open zones on the partition/partitions
involved, or there are other conditions
present which lower system security,
nonetheless, the user arms the system.
One event for each
partition
Yes
Failed to arm
The “OpenZonesArmLock” option is
enabled at the time of a partition arming
command and there is at least one open
zone on the partition/s involved.
or
when one or more of the conditions
described in “LossTamp.ongoing” is pres-
ent (refer to “FaultForNotReady”,
para-
graph 6-27 Other parameters
).
One event for each
partition
Yes
Valid code
A user-code PIN entered at a keypad is
recognized as valid
One event for each
code
Yes
Valid key
A key used at a reader is recognized as
valid on the reader
One event for each key
Yes
Valid Code AtKeyp.
A user-code PIN entered at a keypad is
recognized as valid on the keypad
One event for each
keypad
Yes