60
Options and programming methods
This is the time window during which the system must detect a number of pulses equal
to or higher than the value programmed for “Rollerbl. pulses” before generating a zone
alarm. This window can be expressed in seconds or minutes (see Note).
Rollerbl. pulses
(rollerblind zone)
This is the number of pulses necessary to generate a zone-alarm event. If this value is
more than 1, you must also programme the “Rollerblind time” parameter.
Shock sensit.
(shock (Nessensor) zone)
This is an empirical parameter which regulates the sensitivity of the sensor. Increasing
this value decreases detection sensitivity.
Shock time
(shock (Nessensor) zone)
This parameter applies only when the “Shock pulses” value is more than 1.
This is the window during which a number of pulses must be detected the number of
alarm pulses must equal or exceed the value programmed for “Shock pulses”, before
the system generates an alarm. This window can be expressed in seconds or minutes
(see Note).
Shock pulses
(shock (Nessensor) zone)
This is the number of pulses necessary to generate a zone-alarm event.
If this value is more than 1, you must also programme the “Shock time” parameter.
If this value is 0, the zone alarm will be generated by the “Shock sensit.” parameter.
All the above-mentioned values can be programmed as follows:
1. Use
and
where possible to indicate the time in multiples of 15
millieseconds, seconds or minutes (refer to the note opposite).
2. Use keys
and
to select the field you wish to change, then use the number
keys (
, etc.) to edit the number.
or
Use keys
and
to increase or decrease the number.
3. Press
to confirm and exit.
Via PC
Programming zones via the SmartLeague application is accomplished by the selection
and programming of the terminal configured as zone, described in
paragraph 6-6
Terminals
.
6-8
Outputs
This programming section deals with all the output parameters.
SmartLiving control panels provide 3 outputs:
•
Relay Output
•
O.C. Output 1
•
O.C. Output 2
Via Keypad
1. Access the “Outputs” section.
Type-in Code
(Installer PIN)
, PROGRAMMING Outputs
.
2. Use
and
to select the output thenpress
.
Description
This is the editable output label (device description). At default all the outputs, except
for the 3 outputs on the control panel motherboard, assume the description of the
peripheral they refer to followed by the respective terminal.
Follow the instructions in
paragraph 6-7 Zones - Descriptions
.
Output options
Use
and
to enable or disable the selected option.
•
Norm. closed
: this will be the output status during standby.
•
Monostable
(On for a period of time)
•
Buzzer (beeper)
: generates a 1Khz signal when the output activates - can be used
to drive a buzzer.
If this value is
expressed in
minutes, there is an
error margin of one
minute (for example, if you
set 5 minutes, the effective
period can vary between 4
and 5 minutes).
RELAY 001
Description
Output options
Monostable time
PROGRAMMING
Terminals
Zones
Outputs
Outputs
RELAY 001
OUTPUT 001
OUTPUT 002