FP
Σ
13.1 Table of Specifications
13 - 5
13.1.2
Performance Specifications
Item
Descriptions
FPG-C32T
FPG-C32T2
FPG-C24R2
Number of control-
lable I/O points
Control unit
32 points (DC input:
16, Transistor out-
put: 16)
32 points (DC input:
16, Transistor out-
put: 16)
24 points (DC input:
16, Relay output: 8)
When using FP0 expan-
sion units
Max. 128 points (up
to 3 units)
Max. 128 points (up
to 3 units)
Max. 120 points (up
to 3 units) *When
using transistor out-
put type expansion
units
When using FP
Σ
expan-
sion units
Not possible
Max. 288 points (up
to 4 units)
Max. 280 points (up
to 4 units) *When
using transistor out-
put type expansion
units
When using FP0 and
FP
Σ
expansion units
—
Max. 384 points (up
to FP0 3 units and
FP
Σ
4 units)
Max. 376 points (up
to FP0 3 units and
FP
Σ
4 units) *When
using transistor out-
put type expansion
units
Programming method/Control method
Relay symbol/Cyclic operation
Program memory
Built-in Flash ROM (without backup battery)
(By using exclusive instructions it is possible to write and read
data.)
Program capacity
12,000 steps
Number of instruction
Basic
85
High-level
220
Operation speed
0.4
µ
s/step (by basic instruction)
Operation
memory
points
Relay
External input relay (X)
512 points
(
*
Note 7)
1,184 points
(
*
Note 7)
1,184 points
(
*
Note 7)
points
External output relay (Y)
512 points
(
*
Note 7)
1,184 points
(
*
Note 7)
1,184 points
(
*
Note 7)
Internal relay (R)
1,568 points (R0 to R97F) (
*
Note 1)
Timer/Counter (T/C)
1,024 points (
*
Note 1 and 2) (for initial setting, Timer: 1,008
points (T0 to T1007), Counter: 16 points (C1008 to C1023)
Timer:
Can count up to (in units of 1 ms, 10 ms, 100 ms, or 1
s) x 32767.
Counter: Can count up to 1 to 32767.
Link relays (L)
1,024 points (
*
Note 1)
Memory
area
Data register (DT)
32,765 words (DT0 to DT32764) (
*
Note 1)
area
Link data register (LD)
128 words (
*
Note 1)
Index register (I)
14 words (I0 to ID)
Differential points
Unlimited of points
Master control relay points (MCR)
256 points
Number of labels (JP and LOOP)
256 labels
Number of step ladders
1,000 stages
next page
Summary of Contents for FP Series
Page 15: ...FP Functions and Restrictions of the Unit 1 2...
Page 25: ...FP Specifications and Functions of Control Unit 2 2...
Page 37: ...FP Expansion 3 2...
Page 44: ...Chapter 4 I O Allocation 4 1 I O Allocation 4 3...
Page 45: ...FP I O Allocation 4 2...
Page 51: ...FP Installation and Wiring 5 2...
Page 77: ...FP High speed Counter and Pulse Output Functions 6 2...
Page 133: ...FP High speed Counter and Pulse Output Functions 6 58...
Page 135: ...FP Communication Cassette 7 2...
Page 147: ...FP Communication Function 1 Computer Link 8 2...
Page 169: ...FP Communication Function 2 General purpose Serial Communication 9 2...
Page 205: ...FP Communication Function 2 General purpose Serial Communication 9 38...
Page 207: ...FP Communication Function 3 PLC Link Function 10 2...
Page 232: ...Chapter 11 Other Functions 11 1 Analog Potentiometer 11 3 11 2 Clock Calendar Function 11 4...
Page 233: ...FP Other Functions 11 2...
Page 239: ...FP Self Diagnostic and Troubleshooting 12 2...
Page 249: ...FP Self Diagnostic and Troubleshooting 12 12...
Page 251: ...FP Specifications 13 2...
Page 323: ...Index FP I 4...
Page 325: ...FP Record of changes R 2...