6.4 Pulse Output Function
6 - 33
(*1): Control code (H constant)
Operation mode
0: Incremental
Specifies the amount of travel (number of pulses)
1: Absolute
Specifies the target value (absolute value)
H
j j j
Upper word
0: Fixed
Duty (on width)
0: Duty 1/2 (50%)
1: Duty 1/4 (25%)
Frequency range
0: 1.5 Hz to 9.8 kHz
1: 48 Hz to 100 kHz
2: 191 Hz to 100 kHz
Output method
0: CW
(addition counting)
1: CCW
(subtraction counting)
2: PLS+SIGN (forward off) (addition counting)
3: PLS+SIGN (reverse on) (subtraction counting)
4: PLS+SIGN (forward on) (addition counting)
5: PLS+SIGN (reverse off) (subtraction counting)
j j
j j j
(
*
2): Frequency (Hz) “K constant”
1.5 Hz to 9.8 kHz [K1 to K9800 (units: Hz)] (Max. error near 9.8 kHz: approx. -0.9 kHz)
* Set “1” to specify 1.5 Hz.
48 Hz to 100 kHz [K48 to K100000 (units: Hz)] (Max. error near 100 kHz: approx. -3 kHz)
191 Hz to 100 kHz [K191 to K100000 (units: Hz)] (Max. error near 100 kHz: approx. -0.8 kHz)
(
*
3): Target value (K-2147483648 to K2147483647)
The value of the 32-bit data specified for the target value should be within the range indicated in
the table below.
Specification of control code
Range of allowable target values
Operation mode
Output method
Range of allowable target values
Incremental
Addition counting
Specifies a positive value.
Subtraction counting
Specifies a negative value.
Absolute
Addition counting
Specifies a value larger than the current value
Subtraction counting
Specifies a value smaller than the current value
Trigger
R10
R903A
(R903C)
5,000
Frequency (speed) [Hz]
01000
8000 10000
Elapsed value of
high-speed
counter
(Amount of travel)
1,000
2,500
3000
Pulse output diagram
When the execution condition (trigger) R10 of the
F174 (SP0H)
instruction goes on, the
high-speed counter control flag R903A (R903C) goes on. When the elapsed value
reaches 10,000 and pulse output stops, R903A (R903C) goes off.
Summary of Contents for FP Series
Page 15: ...FP Functions and Restrictions of the Unit 1 2...
Page 25: ...FP Specifications and Functions of Control Unit 2 2...
Page 37: ...FP Expansion 3 2...
Page 44: ...Chapter 4 I O Allocation 4 1 I O Allocation 4 3...
Page 45: ...FP I O Allocation 4 2...
Page 51: ...FP Installation and Wiring 5 2...
Page 77: ...FP High speed Counter and Pulse Output Functions 6 2...
Page 133: ...FP High speed Counter and Pulse Output Functions 6 58...
Page 135: ...FP Communication Cassette 7 2...
Page 147: ...FP Communication Function 1 Computer Link 8 2...
Page 169: ...FP Communication Function 2 General purpose Serial Communication 9 2...
Page 205: ...FP Communication Function 2 General purpose Serial Communication 9 38...
Page 207: ...FP Communication Function 3 PLC Link Function 10 2...
Page 232: ...Chapter 11 Other Functions 11 1 Analog Potentiometer 11 3 11 2 Clock Calendar Function 11 4...
Page 233: ...FP Other Functions 11 2...
Page 239: ...FP Self Diagnostic and Troubleshooting 12 2...
Page 249: ...FP Self Diagnostic and Troubleshooting 12 12...
Page 251: ...FP Specifications 13 2...
Page 323: ...Index FP I 4...
Page 325: ...FP Record of changes R 2...