4.1 I/O Allocation
4 - 5
4.1.3
I/O Number of FP0 Expansion Unit (for right side expansion)
I/O do not need to be set as I/O allocation is performed automatically when an
expansion unit is added. The I/O allocation of expansion unit is determined by the
installation location.
Type of expansion unit
First expansion
Second expansion
Third expansion
E8X
Input (8 points)
X20 to X27
X40 to X47
X60 to X67
E8R
Input (4 points)
X20 to X23
X40 to X43
X60 to X63
E8R
Output (4 points)
Y20 to Y23
Y40 to Y43
Y60 to Y63
E8YR/E8YT/E8YP
Output (8 points)
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16X
Input (16 points)
X20 to X2F
X40 to X4F
X60 to X6F
E16R/E16T/E16P
Input (8 points)
X20 to X27
X40 to X47
X60 to X67
E16R/E16T/E16P
Output (8 points)
Y20 to Y27
Y40 to Y47
Y60 to Y67
E16YT/E16YP
Output (16 points)
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
E32T/E32P
Input (16 points)
X20 to X2F
X40 to X4F
X60 to X6F
E32T/E32P
Output (16 points)
Y20 to Y2F
Y40 to Y4F
Y60 to Y6F
4.1.4
I/O Number of FP0 Analog I/O Unit (for right side expansion)
The I/O allocation of FP0 analog I/O unit “FP0-A21” is determined by the installation
location.
Unit
First expansion
Second expansion
Third expansion
Input
CH0 (16 points)
WX2 (X20 to X2F)
WX4 (X40 to X4F)
WX6 (X60 to X6F)
Input
CH1 (16 points)
WX3 (X30 to X3F)
WX5 (X50 to X5F)
WX7 (X70 to X7F)
Output (16 points)
WY2 (Y20 to Y2F)
WY4 (Y40 to Y4F)
WY6 (Y60 to Y6F)
4.1.5
I/O Number of FP0 A/D Conversion Unit (for right side expansion)
The I/O allocation of FP0 A/D conversion unit “FP0-A80” is determined by the
installation location.
The data for the various channels is converted and loaded with a user program that
includes a switching flag to convert the data.
Unit
First expansion
Second expansion
Third expansion
CH0 (16 points)
CH2 (16 points)
WX2 (X20 to X2F)
WX4 (X40 to X4F)
WX6 (X60 to X6F)
CH4 (16 points)
WX2 (X20 to X2F)
WX4 (X40 to X4F)
WX6 (X60 to X6F)
Input
CH6 (16 points)
Input
CH1 (16 points)
CH3 (16 points)
WX3 (X30 to X3F)
WX5 (X50 to X5F)
WX7 (X70 to X7F)
CH5 (16 points)
WX3 (X30 to X3F)
WX5 (X50 to X5F)
WX7 (X70 to X7F)
CH7 (16 points)
Summary of Contents for FP Series
Page 15: ...FP Functions and Restrictions of the Unit 1 2...
Page 25: ...FP Specifications and Functions of Control Unit 2 2...
Page 37: ...FP Expansion 3 2...
Page 44: ...Chapter 4 I O Allocation 4 1 I O Allocation 4 3...
Page 45: ...FP I O Allocation 4 2...
Page 51: ...FP Installation and Wiring 5 2...
Page 77: ...FP High speed Counter and Pulse Output Functions 6 2...
Page 133: ...FP High speed Counter and Pulse Output Functions 6 58...
Page 135: ...FP Communication Cassette 7 2...
Page 147: ...FP Communication Function 1 Computer Link 8 2...
Page 169: ...FP Communication Function 2 General purpose Serial Communication 9 2...
Page 205: ...FP Communication Function 2 General purpose Serial Communication 9 38...
Page 207: ...FP Communication Function 3 PLC Link Function 10 2...
Page 232: ...Chapter 11 Other Functions 11 1 Analog Potentiometer 11 3 11 2 Clock Calendar Function 11 4...
Page 233: ...FP Other Functions 11 2...
Page 239: ...FP Self Diagnostic and Troubleshooting 12 2...
Page 249: ...FP Self Diagnostic and Troubleshooting 12 12...
Page 251: ...FP Specifications 13 2...
Page 323: ...Index FP I 4...
Page 325: ...FP Record of changes R 2...