Operating Instructions EBL512, V1.44.x
82
27.2
Calibration of monitored outputs (H5/A1)
The voltage outputs (S0-S3) in each control unit are monitored
(supervised), as well as the outputs (0-3) in each output unit type 2262
and 2263. A calibration has to be performed to ensure the function.
When all alarm devices (sounders, etc.) have been connected,
including required resistors and when the SSD download is ready,
calibration has to be done as follows.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
programming (H5)", see
page 81.
Calibration of monitored outputs
ACCEPT? A1
"A"
Calibration in process
Please wait......
Calibration of monitored outputs
ACCEPT? A1
Calibration is ready.
Scroll or push "Return" to
H5. Scroll or push
"Return" to logout.