Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
92
28
Acknowledge FAULTS (H6)
LEDs "Fault tx" (L19) and "Fault" (L8) are lit and resp. outputs are
activated. There is a fault message shown in the FBP display(s). More
than one fault is indicated in the display by the text:
More faults
If a fault is automatically corrected, before being acknowledged, it is
indicated in the display by the text:
Serviced
NOTE! The fault still has to be acknowledged in menu H6.
In menu H6 are all faults listed (not acknowledged and acknowledged
but not corrected faults).
All faults / fault status are stored in the event log and can be listed, see
chapter "Show event log (H4/U8)", page 78.
When
all
faults are, the LED "Fault tx" will be turned off.
Corresponding outputs will be reset.
When
all
faults are acknowledged and corrected (serviced), LED
"Fault" will be turned off. Corresponding outputs will be reset.
Also see chapter "Fault", page 35.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H6.
Acknowledge FAULTS
ACCEPT? H6
"A"
FAULT: Xxxxxxxx............
Date: MM-DD Time: HH:MM See comments
This is a list in which
you can scroll. If the
fault is corrected, the
text:
Serviced
is
shown. To acknow-
ledge the fault shown in
the display, push "Fault
acknowledged"
"Fault acknowledged"
FAULT: Xxxxxxxx............
Date: MM-DD Time: HH:MM Acknowledged
The fault is now acknow-
ledged. If / when it is
corrected, it's no more
shown in this list. Scroll
to find more faults to be
acknowledged, or push
"Return" to menu H6.
"Return"
Acknowledge FAULTS
ACCEPT? H6
Scroll or push "Return"
to logout.