18 Programming
(SSD
download)
The PC program
Win512
is used for programming (download) of the
site specific data (SSD).
When the control units is running (power supplied) and when
required, the TLON network programming (configuration) is done, the
SSD download can start.
The PC has to be connected to the "D" connector J1 in the control unit
(main board 1556). Start Win512. Now you have to be authorised,
i.e. you have to log on
39
to the control unit.
18.1
Single Control Unit
Start the downloading from Win512.
After the downloading, an automatic reset/restart will take place (see
chapter "Reset / Restart", page 55.
18.2
Control Units in a TLON network
The PC should be connected to one control unit, from which the SSD
for all control units can be downloaded. In Win512, you select the
control unit(s) to which the SSD should be downloaded.
40
Start the downloading from Win512.
After the downloading in the selected control unit, an automatic
reset/restart will take place in that control unit (see chapter "Reset /
Restart", page 55.
If you select two or more control units, the PC has to be connected to
a control unit that shall have no SSD downloaded or to the control unit
that has the highest number (address), because after the downloading
to a control unit, an automatic reset/restart will take place in that
control unit and the downloading will start in the next selected control
unit.
41
Regarding the automatic reset/restart, see chapter "Reset /
39
Access code for level 5 should be entered via the PC (Win512).
40
It is recommended to select only one control unit at a time but of course, it
is depending of the SSD quantity (number of COM loop units, texts, outputs,
etc.) and up to three control units are normally okay. NOTE! After the
automatic reset/restart of a control unit, a number of faults could be
generated. This will cause "heavy traffic" on the network, which could affect
the SSD downloading to other control units.
41
Downloading is performed in a consecutive order, i.e. 0-1-2-3-4-……-29
(amongst the selected control units).