Perform monthly test (H1)
The control unit and the installation should be tested on a regular
basis. If one twelfth of the alarm points are tested each month, the
whole installation will be tested after one year.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. If a real fire alarm is
generated by
an alarm point not in test mode
, the normal fire alarm
functions will be activated, i.e. outputs (sounders), routing equipment
(fire brigade tx) etc. will be activated.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) may be disabled (if programmed so in
Win512). There will be an automatic test mode exit one hour after the
latest tested alarm point.
See also chapter "Perform ZONE TEST (test mode) (H7)
to be continued
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Perform monthly test
ACCEPT? H1
"A"
Check that all LEDs light up!
ACCEPT
"A"
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒ ▒
The buzzer (in the C.U.)
sounds and all dots in the
display are shown for 3
seconds. When printer is
available, it will print out:
ABCDE…………Z
abcde…………z
Zone to be set in TEST MODE:
??? ??? ??? ??? Start test: ACCEPT
Write zone numbers
(e.g. 001, 002, 003,
004)
Zone to be set in TEST MODE:
001 002 003 004 Start test: ACCEPT
Push "A" to start the test
mode.
"A"
Zones are set in test mode
wait....
LED "Test mode" (L9)
will light up.
Zone in TEST MODE:
001 002 003 004 End test: ACCEPT
Perform the tests. When
ready push "A".