Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
67
24.7
Re-enable non-reset zone / address (H2/B7)
This function is normally only used in the Swedish configuration
(Convention = RUS in Win512).
One or more alarm points have been reset when still in alarm status
(e.g. smoke in a sensor or activated manual call point). To prevent an
immediate new fire alarm, these alarm points have been
"encapsulated", indicated by LED "Zone/Detector not reset" (L6), and
have to be re-enabled before the can generate a new fire alarm.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H2:
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B7.
Re-enable non-reset zone / address
ACCEPT? B7
"A"
Zone/address 000/00 non-reset
Re-enable: push ACCEPT? L
If there are no zone /
addresses to re-enable,
menu B7 will be shown
again.
If it's the correct zone /
address to re-enable, push
"A" to accept. If not, scroll
or write the wanted zone /
address and push "A" to
accept.
"A"
Re-enable non-reset zone / address
ACCEPT? B7
If more re-enablements
shall be done, continue like
above. If not, scroll or
push "Return" to menu H2.
Scroll or push "Return" to
logout.