Operating Instructions EBL512, V1.44.x
52
19
New system program (SW) version
download
SW download is normally factory made before delivery. Latest SW
version is then downloaded.
Due to continual development and improvement, different SW
versions could be found.
If you wish to download a new software (system program) version, a
PC and
Win512
is used. Before download, the PC has to be
connected to the "D" connector J1 in the control unit (main board
1556) in question.
43
1.
Start Win512.
2.
Set jumper "JP1 (BOOT)" in position on the main board 1556.
3.
Do a reset/restart by setting jumper "JP4 (RESET)" momentarily
in position (approx. 1 second).
4.
The buzzer will now sound intermittent and LED "LD101" starts
blinking, indicating that the control unit is in "Bootstrap mode".
5.
Start the downloading. The buzzer will now be silenced.
6.
When the download is ready, in the Win512 log view it will be
shown: "Download ready".
7.
Reset jumper "JP1 (BOOT)" (position OFF) and do a reset/restart,
see paragraph 2 above. Regarding the reset/restart, see chapter
"Reset / Restart", page 55.
Follow the same procedure in each control unit.
19.1
Control Units in a TLON network
All control units connected to a TLON network
should
have the same
SW version.
For download of new SW in each control unit, follow the procedure
above.
43
In old control units, a separate CPU board (1526) could be found.
Regarding connections, jumpers and LEDs, see documentation valid for that
HW.