Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
47
16.2 Fault
acknowledge
The LEDs "Fault tx" and "Fault" are lit.
A fault message, date and time are shown in the FBP display(s).
After the time may be shown
More faults
= more than one fault is
generated in the system..
If
Fault latching
is selected in Win512, after the time may be shown
Serviced
= the fault is already corrected.
•
Login, according to chapter "Access", page 57.
•
Use menu H6 (access level 2) for fault acknowledge, see
chapter "Acknowledge FAULTS (H6)", page 92.
•
All faults have to be individually acknowledged. Use
↑
or
↓
keys to scroll.
•
If a fault has been corrected before it has been
acknowledged, the text
Serviced
is added after the time.
It still has to be acknowledged.
•
When a fault is corrected and acknowledged, it will
disappear from the list (H6).
•
When
all
faults have been acknowledged, the LED "Fault
tx" will be turned off and output(s) for routing equipment
(Fault tx) is(are) reset.
•
As long as there are faults (not acknowledged faults and/or
acknowledged but not corrected faults) the LED "Fault" will
be lit and corresponding output(s) activated.
The list in menu H6, shows a maximum of 120 faults (not
acknowledged faults and/or acknowledged but not corrected faults).
When a fault is acknowledged and corrected it will be removed from
the list and a new fault can be shown. Corrected faults are shown in
the event log (menu H4/U8).