Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
83
27.3
Sensitive fault detection mode (H5/A2)
To increase the possibilities to detect faults during the commissioning,
it is possible to use the "Sensitive fault detection mode. (The time
delay for each fault will be reduced).
NOTE!
Don't forget to turn off this mode after the commissioning.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
programming (H5)", see
page 81.
Scroll to menu A2
Sensitive fault detection mode
ACCEPT? A2
"A"
Sensitive fault detection mode: 0
(0 = off, 1 = on)
Push "A" or "1" and "A" to
accept. ON is indicated by
LED "Fault". This mode
is ON until turned OFF in
this menu (A2).
"A"
or
"1", "A"
Sensitive fault detection mode
ACCEPT? A2
Scroll or push "Return" to
H5. Scroll or push
"Return" to logout.