Operating Instructions EBL512, V1.44.x
53
20
EBL512 settings download
EBL512 settings are normally factory made before delivery. On site,
it is possible to download the following:
•
The number of addresses (max. loop units)
44
•
Convention (different functions / facilities, country depending)
•
Language
If you wish to download new EBL512 settings, a PC and
Win512
is
used. Before download, the PC has to be connected to the "D"
connector J1 in the control unit (main board 1556) in question.
45
1.
Start Win512.
2.
Set jumper "JP1 (BOOT)" in position on the main board 1556.
3.
Do a reset/restart by setting jumper "JP4 (RESET)" momentarily
in position (approx. 1 second).
4.
The buzzer will now sound intermittent and LED "LD101" starts
blinking, indicating that the control unit is in "Bootstrap mode".
5.
The "Win512 settings" dialog box shows default settings in the
different fields. Click the "Read" button to see the actual settings.
Then write the new settings in the fields respectively.
6.
Start the downloading. The buzzer will now be silenced.
7.
When the download is ready, in the Win512 log view it will be
shown: "Download ready".
8.
Click the "Read" button to verify the new settings.
9.
Reset jumper "JP1 (BOOT)" (position OFF) and do a reset/restart,
see paragraph 2 above. Regarding the reset/restart, see chapter
"Reset / Restart", page 55.
Follow the same procedure in each control unit.
44
To change the "Max. loop units", a separate download password is
required. This password is in conjunction with a "Key" (eight digits) and is
available from the producer if you are authorized. The Key is shown in
Win512 and the procedure is described in the Win512 help.
45
In old control units, a separate CPU board (1526) could be found.
Regarding connections, jumpers and LEDs, see documentation valid for that
HW.