Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
68
24.8
Control on / Control off (H2/B8)
Outputs programmed as type 0 = control (general), type 1 = fire
ventilation and/or type 2 = extinguishing system
50
can be disabled all
at the same time.
Control off
means that even if the control condition
(expression) for resp. output is fulfilled, the outputs will not be
activated.
Control off is indicated by LED "Disabled" and is shown in menu
H4/U1.
Don't forget to re-enable the outputs again,
i.e.
Control on
via
menu H2/B8.
50
Also the "Extinguish equipment output" on the German FBP interface
board 1583.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 57.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B8.
Control on / Control off
ACCEPT? B8
"A"
Control off (=0) or control on (=1)? 1
ACCEPT?
Push "1" or "0" and push
"A" to accept.
"A"
Control on / Control off
ACCEPT? B8
Scroll or push "Return" to
menu H2. Scroll or push
"Return" to logout.