Matsushita Electric Works Fire & Security Technology AB
MEW00442
Rev: -
Operating Instructions EBL512, V1.44.x
102
30.8
Synchronize the control units (H8/S7)
The control units have to be synchronized when:
•
The following fault message is shown:
FAULT: CU xx has wrong information
60
•
After "Status Checking" has been enabled in Win512.
(When using Win512, you can use the "Synchronize" toolbar button.)
Action
Text in display
Comments
"Access"
According to chapter
"Access code for
maintenance", see page 95.
Scroll to menu S7.
Synchronize the control units
ACCEPT? S7
"A"
Shall control units be synchronized? 0
(1 = Yes, 0 = No) ACCEPT?
Push "A" to start the
synchronisation.
"A"
Synchronization will take about 30 sec
for each CU. Hit any key to return.
Push "Return" at once.
"Return"
Shall control units be synchronized? 0
(1 = Yes, 0 = No) ACCEPT?
Before a new syncro-
nization, wait until the
syncronization is ready.
61
Push "Return" to menu S7.
"Return"
Synchronize the control units
ACCEPT? S7
Scroll or push "Return" to
menu H8. Scroll or push
"Return" to logout.
60
If the control unit restart in conjunction with this fault, the synchronization
will happen automatically.
61
Normally a syncronization is done in conjunction with the fault message
above. When the syncronization is ready the fault will be indicated as
"Serviced". If a syncronization is done via Win512 (i.e. normally no fault
message) there is no syncronization ready indication. The syncronization
time is depending on the amount of data (faults, disablements, etc.) stored. If
a new syncronization is started before a syncronization is ready, the
syncronization will start from the beginning again.