Warning Sign – Installation Guide 

Item Numbers – 4210-0110 & 4210-0120 

www.ampac.net   

MAN3056-2                                                                                                                                                                                   Page 1 of 3 

Introduction 

 
The  AMPAC  Warning  Signs  provide  clear,  visual  and 
audible  indication  of  an  alarm  event  and  are  designed 
for use with fire detection and alarm systems which may 
incorporate  agent  release  capability.  The  display  may 
also be customised as required to cater for a variety of 
applications. 
 
The  Warning  Signs  are  available  in  two  standard 
formats, the 4210-0110 for semi-flush or surface mount 
indoor  applications  while  the  4210-0120  affords  IP65 
weatherproof capability for outdoor applications. 
 
The Warning Signs incorporate a split level design that 
enables  two  text  messages  to  be  independently 
controlled through the application of input voltages. The 
two  levels  may  be  activated  by  either  a  voltage 
reversing DC input or through application of a common 
positive and two switched negative DC inputs. 
  
Option  switches  located  inside  the  unit  enable  the 
commissioning  engineer  to  further  configure  the 
Warning  Sign  for  continuous or  flashing  Red  or  Yellow 
LEDs,  enable  an  integral  buzzer  in  continuous  or 
pulsing  mode  of  operation,  to  enable  a  mute  facility  to 
silence  the  buzzer  and  or  optional  external  sounder.  A 
facility  to  synchronise  the  flashing  between  multiple 
signs is also provided. 
 
Illuminated  using  the  latest  in  high  efficiency,  high 
intensity  LEDs  to  greatly  reduce  power  consumption 
and  increase  reliability  ensures  that  the  brightness  is 
maintained  even  when  running  on  depleted  stand-by 
batteries. 
 

Note:  A  maximum  of  6  AMPAC  Warning  Signs  can 
be  connected  to  the  output  of  the  Agent  Release 
Board. 

 

Installation (4210-0110 enclosure) 

Open  the  outer  door  using  the  plastic  key  device 
provided.  Using  the  back  box  as  a  template,  mark  the 
position of the four fixings in the required position on the 
mounting surface. For semi-flush fixing applications, cut 
a hole in the mounting surface to the dimensions shown 
below ensuring adequate depth is provided for the unit 
to be recessed.  

 

Before  fixing  the  unit  decide  which  entry  points  are  to 
be  used  for  the  in-coming  cables.  The  back box  has 7 
20mm  knockouts  in  the  top  and  bottom  which  can  be 

easily  removed  by  sharply  tapping  them  with  a  blunt 
instrument and hammer.  
 
Top  entry  is  recommended  on  this  product  however, 
back  entry  can  be  achieved  by  drilling  additional  holes 
in  the  back  box  to  suite.  Fix  the  back  box  to  the 
mounting  surface  using  4  appropriate  sized  bolts  or 
screws and install the acrylic text fascia plate using the 
6 screws provided. 
 

Installation (4210-0120 - weatherproof enclosure) 

The weatherproof enclosure should be surface mounted 
using appropriate fixings and sealing washers.  

o

 

Using  the  6x  outer  screws,  remove  the  clear 
Perspex lid.  

o

 

Using  the  4x  black  dome  nuts,  remove  the  text 
legend fascia plate bezel. 

o

 

Remove the internal printed circuit board using the 
2x screws located in the centre of the PCB. 

o

 

Drill 4x 4mm fixing holes in the rear of the back box 
near  each  corner  and  fix  the  back  box  to  the  wall 
using  appropriate  fixing  screws  or  bolts.  Ensure 
that  a  watertight  seal  is  maintained  around  the 
fixing holes. 

o

 

Re-instate  the  printed  circuit  board  and  fit  the 
acrylic  text  legend  to  the  fascia  plate  bezel  using 
the 6x M4 nuts provided. 

o

 

It  is  recommended  that  the  fascia  plate  bezel 
complete  with  acrylic  text  legend  should  be  re-
instated following initial testing of the system. 

 

Cabling 

The  maximum  size  of  cable  that  the  terminals  will 
accommodate  is  2.5mm².  The  interconnecting  external 
cables  should  be  connected  to  the  back  box  using 
suitable  cable  glands.  On  the  4210-0120  back  box, 
waterproof lock-tight glands should be used to ensure a 
weatherproof seal is maintained. Ensure that cable tails 
of  sufficient  length  are  maintained  to  reach  the 
terminals without cutting across the front surface of the 
internal  printed  circuit  board  as  this  will  impair  the 
illumination of the sign.  
 
The Warning Sign can be configured to illuminate in two 
ways.  For  voltage  reversal,  2  wire  applications  and  for 
use  with  the  AMPAC  Agent  Release  module,  refer 
figure 1. For common positive, switched negative 3 wire 
applications, refer figure 2. 
 

Configuration Switches 

The  Warning  Sign  can  be  configured  to  operate  in  a 
variety  of  ways  using  DIL  switches  located  on  the 
printed circuit board. Table 1 outlines the functionality of 
the on-board switches located at SW2, switches 1 - 8.  
 
SW1  controls  the  colour  of  the  LEDs  during  the 
operation of the sign, Red or Yellow and should be set 
to suit the application of the Warning Sign.  
 