7 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
80
3587317/21 EN
TAPCON
®
2. Go to
Settings > Commissioning wizard
.
Figure 68: Calling up the commissioning wizard
3. Press the
Next
button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning,
continue with the function test [
7.5 Function tests
Before switching from manual mode to auto mode, Maschinenfabrik Rein-
hausen recommends carrying out function tests. These function tests are de-
scribed in the following sections. Note the following points for all function
tests:
▪ You must ensure that REMOTE mode is disabled before you can control
the on-load tap-changer manually in manual mode.
▪ You can only activate the on-load tap-changer manually in manual mode
using the
and
keys.
▪ You have to be logged in to the device as a user with a parameter config-
urator or administrator user role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
During the function test, you must set the most important parameters. Details
on the parameters listed can be found in the Operation [
87] chapter.