8 Operation
Maschinenfabrik Reinhausen GmbH 2020
233
3587317/21 EN
TAPCON
®
Correction factor and offset
Setting a correction offsets systematic errors of the analog signals. The cor-
rection is determined by multiplying a factor by the sum of the offset. The
minimum and maximum values of the function values apply as a limit value
for the correction. There is no limit for the correction offset.
Max.
Min.
Measured variable
Max.
Min.
Analog signal
Correction factor
Correction offset
Figure 164: Analog signal with linear characteristic curve, correction factor <1 and correction off-
set
NOTICE
Damage to the device and sensors!
Incorrectly connected and configured analog inputs/outputs may result in
damage to the device and sensor.
► Follow information about connecting analog sensors.
► Configure analog inputs and outputs according to the connected sensors.
The following information is displayed in tabular form for configuring the ana-
log inputs and outputs. Grayed-out elements cannot be changed.
Property
Options
Function
Function of the analog input (I: ...) or the analog output
(O: ...). You can adjust the designation.
Signal type
Select signal type of analog sensor or deactivate analog
output.
▪ 4...20 mA
▪ PT100-2/3/4, PT1000-2/3/4
Card/channel
Select the slot and channel of the analog sensor. Note the
connection diagram supplied.
Unit
1)
Set the unit of the signal.
Decimal places
1)
Set up to three decimal places.
Minimum/maximum
value
Set the minimum and maximum values of the sensor, e.g.
with a 4...20 mA signal, the corresponding measured
value for 4 mA and the corresponding value for 20 mA.