14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
306
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
Q<< hysteresis
0...10,000 kVar
1,000 kVar
Q<< delay time
0.0...60.0 s
5.0 s
Q> [kVar]
-100,000...100,000 kVar
10,000 kVar
Q> hysteresis
0...10,000 kVar
1,000 kVar
Q> delay time
0.0...60.0 s
5.0 s
Q>> [kVar]
-100,000...100,000 kVar
10,000 kVar
Q>> hysteresis
0...10,000 kVar
1,000 kVar
Q>> delay time
0.0...60.0 s
5.0 s
cos φ <
0.00...1.00
0.85
cos φ < hysteresis
0.00...0.10
0.01
cos φ < delay time
0.0...60.0 s
5.0 s
cos φ <<
0.00...1.00
0.80
cos φ << hysteresis
0.00...0.10
0.01
cos φ << delay time
0.0...60.0 s
5.0 s
Settings > Parameters > Reversal of power flow
Reversal of power flow hysteresis 0.0...100.0 MW
0.1 MW
Reversal of power flow delay time 0.0...60.0 s
5.0 s
Behavior for reversal of power
flow
Off, Target-tap-position
operation, Auto blocking,
Auto/manual blocking
Off
Settings > Parameters > Tap position monitoring
Pos <
-128...128
0
Pos < delay time
0.0...60.0 s
0.0 s
Pos < behavior
Off, Auto blocking posi-
tion-, Auto/manual block-
ing position-
Off
Pos >
-128...128
0
Pos > delay time
0.0...60.0 s
0.0 s
Pos > behavior
Off, Auto blocking position
+, Auto/manual blocking
p
Off
Settings > Parameters > Bandwidth monitoring
Function monitoring
Off, Auto, Auto/manual
Off
Hysteresis for function monitoring 0.00...1.00%
0.00%
Function monitoring delay time
1...60 min
15 min
Hysteresis for lower bandwidth
0.00...1.00%
0.00%
Lower bandwidth delay time
0.0...60.0 s
0.0 s
Hysteresis for upper bandwidth
0.00...1.00%
0.00%