8 Operation
Maschinenfabrik Reinhausen GmbH 2020
151
3587317/21 EN
TAPCON
®
Desired
value
BCD input
100
80
40
20
10
8
4
2
1
127 V
1
0
0
1
0
0
1
1
1
128 V
1
0
0
1
0
1
0
0
0
129 V
1
0
0
1
0
1
0
0
1
130 V
1
0
0
1
1
0
0
0
0
131 V
1
0
0
1
1
0
0
0
1
132 V
1
0
0
1
1
0
0
1
0
133 V
1
0
0
1
1
0
0
1
1
134 V
1
0
0
1
1
0
1
0
0
135 V
1
0
0
1
1
0
1
0
1
136 V
1
0
0
1
1
0
1
1
0
137 V
1
0
0
1
1
0
1
1
1
138 V
1
0
0
1
1
1
0
0
0
139 V
1
0
0
1
1
1
0
0
1
140 V
1
0
1
0
0
0
0
0
0
Table 43: BCD-coded desired value
Setting desired value 1
1. Go to
Settings > Parameters > Grid > Control > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Bandwidth
You can use this parameter to set the maximum permissible deviation of the
measured voltage U
actual
from the desired value U
desired
.
In order to set the correct value, the transformer step voltage and nominal
voltage must be known. Note that a large bandwidth will result in a large
control deviation.
The bandwidth must always be greater than the following value:
|
±
B
|
≥ 0,6×
U
n
- 1
-
U
n
U
N
× 100
%
U
n-1
Step voltage of tap position n-1
U
n
Step voltage of tap position n
U
N
Nominal voltage