8 Operation
Maschinenfabrik Reinhausen GmbH 2020
249
3587317/21 EN
TAPCON
®
► Go to
Information > System > Software
.
8.27.3 Parallel operation
In the parallel operation menu, you can display information about the de-
vices that are connected by CAN bus.
Description
Parallel operation status:
▪ Gray = Independent mode
▪ Blue = Parallel operation is active
▪ Red = Parallel operation error
CAN addr.
CAN bus address
Grp.
Parallel operation group
Method
Active parallel operation method
Current tap position
U [V]
Voltage
I_p [%]
Active current
I_q [%]
Reactive curr.
Blocking:
▪ Gray: Parallel operation not blocked
▪ Red: Parallel operation blocked
Table 88: Information about parallel operation
Figure 177: Parallel operation
► Go to
Information > On-load tap-changer regulator > Parallel opera-
tion
.