8 Operation
Maschinenfabrik Reinhausen GmbH 2020
227
3587317/21 EN
TAPCON
®
8.22.1 Setting operator interval for OLTC maintenance
You can define the maintenance interval of your choice for the on-load tap-
changer. You can define the maintenance interval as dependent on time
and/or number of tap-change operations. If the limit is reached (100%), the
device triggers an event message (red).
Settings
Parameters
Maintena...tor
Name
Value
Interval type
Deactivated
Number of tap-change operations
150000
Duration
1.0 a
Date of next maintenance
17.09.2066 23:59:21
Event (yellow)
90.0 %
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 158: Maintenance: OLTC operator
1. Go to
Settings > Parameters > On-load tap-changer > Maintenance:
OLTC operator
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Interval type
You can use this parameter to define the interval type for OLTC mainte-
nance or to deactivate maintenance. You can select the following options:
▪ Deactivated: The maintenance interval is deactivated.
▪ Time: The maintenance interval is dependent on time.
▪ Counter: The maintenance interval is dependent on number of tap-change
operations.
▪ Time and counter: The maintenance interval is dependent on time and
number of tap-change operations. The limit reached first triggers the
event.
Number of tap-change operations
You can use this parameter to define the reading of the tap-change opera-
tion counter at which the device should issue an event message.