8 Operation
Maschinenfabrik Reinhausen GmbH 2020
262
3587317/21 EN
TAPCON
®
Function
If there is a rising edge at Reset, the output value is set
to the value of the Reset value parameter. A rising
edge at Reset takes priority over all other inputs.
For as long as Lock is TRUE, the pulse signal is not
evaluated and the counter reading is retained. If no in-
put is assigned, the default value FALSE is assumed.
When Direction input = FALSE, the output value is in-
cremented by one with every rising edge at the Trigger
input.
When Direction input = TRUE, the output value is
decremented by one with every rising edge at the Trig-
ger input.
Initial state
All inputs and outputs are zero or FALSE.
Table 105: Counter (forwards/backwards) function module
Figure 182: Example of COUNT
1 Trigger
2 Direction
3 Reset
4 Lock
5 Output
8.30.1.3.13 Analog threshold value switch with hysteresis
Designation
THRES, threshold value switch with hysteresis
Inputs
Input (REAL32)
Outputs
Output (BOOL)
Error (BOOL)
Parameter
On Limit (REAL32), -10,000,000… +10,000,000, de-
fault = 10,000,000
Off Limit (REAL32), -10,000,000 … +10,000,000, de-
fault = -10,000,000