15 Technical data
Maschinenfabrik Reinhausen GmbH 2020
326
3587317/21 EN
TAPCON
®
D 4169-09
Standard Practice for Performance Testing of Shipping
Containers and Systems
DC 3, safety level II
IEC 60255-21-1 Class
1
Oscillations (3 cycles, 0.5 g 1 octave/min; 60 cycles, 1.0
g, 1 octave/min)
IEC 60255-21-2 Class
1
Shocks (11 ms, 5 g, 15 g, 3 axes)
IEC 60255-21-3 Class
1
Earthquakes (1...35 Hz; 3.5 mm/1 g horizontal; 1.5
mm/0.5 g vertical; 1 octave/min, 10 min/axis)
Table 152: Environmental durability tests