![MR TAPCON Operating Instructions Manual Download Page 304](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346304.webp)
14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
304
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
U> relative/absolute
Relative, Absolute
Relative
U> [V]
100.0...160.0 V
110.0 V
U> [%]
100.0...140.0%
110.0%
U> hysteresis
0.0...10.0 V
0.0 V
U> delay time
0.5...60.0 s
0.5 s
U> behavior
Off, High-speed return U-,
Auto blocking, Auto/man-
ual blocking
Off
U>> relative/absolute
Relative, Absolute
Relative
U>> [V]
100.0...160.0 V
120.0 V
U>> [%]
100.0...140.0%
120.0%
U>> hysteresis
0.0...10.0 V
0.0 V
U>> delay time
0.5...60.0 s
0.5 s
U>> behavior
Off, High-speed return U-,
Auto blocking, Auto/man-
ual blocking
Off
Settings > Parameter > Current monitoring
I< relative/absolute
Relative, Absolute
Relative
I< [A]
0.00...12.50 A
0.00 A
I< [%]
0.0...250.0%
0.0%
I< hysteresis
0.00...12.50 A
0.00 A
I< delay time
0.0...60.0 s
0.0 s
I< behavior
Off, Auto blocking, Auto/
manual blocking
Off
I<< relative/absolute
Relative, Absolute
Relative
I<< [A]
0.00...12.50 A
0.00 A
I<< [%]
0.0...250.0%
0.0%
I<< hysteresis
0.00...12.50 A
0.00 A
I<< delay time
0.0...60.0 s
0.0 s
I<< behavior
Off, Auto blocking, Auto/
manual blocking
Off
I> relative/absolute
Relative, Absolute
Relative
I> [A]
0.00...12.50 A
10.00 A
I> [%]
50.0...250.0%
110.0%
I> hysteresis
0.00...12.50 A
0.00 A
I> delay time
0.0...60.0 s
0.0 s
I> behavior
Off, Auto blocking, Auto/
manual blocking
Off
I>> relative/absolute
Relative, Absolute
Relative
Summary of Contents for TAPCON
Page 1: ...Voltage regulator TAPCON Operating Instructions 3587317 21 EN ...