8 Operation
Maschinenfabrik Reinhausen GmbH 2020
146
3587317/21 EN
TAPCON
®
Figure 107: Active power-dependent adjustment of desired voltage value
U
ref
Desired value
U
min
Minimum desired value
P
meas
Measured active power
U
max
Maximum desired value
P
min
Active power at minimum de-
sired value
U
0
Set desired value when mea-
sured active power = 0
P
max
Active power at maximum de-
sired value
Response to active power P
max
being exceeded
If the measured active power P
meas
exceeds the set parameter P
max
, the value
U
max
is adopted as the desired value.
U
ref
=
U
max
Response to value falling below active power P
min
If the measured active power P
meas
falls below the set parameter P
min
, the
value U
min
is adopted as the desired value.
U
ref
=
U
min
Response to a measured active power P
meas
= 0 MW:
If the measured active power P
meas
= 0, the set parameter U
0
is adopted.
U
ref
=
U
0