TAPCON
®
starts to count down. Once delay time T2 is complete, a control impulse is
again issued to the motor-drive unit for the tap change
to return to the tol-
erance bandwidth.
Figure 110: Behavior of the regulation function with delay times T1 and T2
1 Upper bandwidth limit
4 Set delay times T1 and T2.
2 Desired value
5 Control variable measured value
3 Lower limit of bandwidth
6 Bandwidth range
A Control variable is outside of the
bandwidth. Delay time T1 starts.
B Delay time T1 complete. Tap
change triggered.
C Delay time T2 complete. Tap
change triggered.
Activate delay time T2
You can use this parameter to activate or deactivate the delay time T2.