14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
305
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
I>> [A]
0.00...12.50 A
10.00 A
I>> [%]
50.0...250.0%
110.0%
I>> hysteresis
0.00...12.50 A
0.00 A
I>> delay time
0.0...60.0 s
0.0 s
I>> behavior
Off, Auto blocking, Auto/
manual blocking
Off
Settings > Parameters > Power monitoring
S< [MVA]
0.0...1,000.0 MVA
0.0 MVA
S< hysteresis
0.0...100.0 MVA
0.1 MVA
S< delay time
0.0...60.0 s
5.0 s
S<< [MVA]
0.0...1,000.0 MVA
0.0 MVA
S<< hysteresis
0.0...100.0 MVA
0.1 MVA
S<< delay time
0.0...60.0 s
5.0 s
S> [MVA]
0.0...1,000.0 MVA
10.0 MVA
S> hysteresis
0.0...100.0 MVA
0.1 MVA
S> delay time
0.0...60.0 s
5.0 s
S>> [MVA]
0.0...1,000.0 MVA
10.0 MVA
S>> hysteresis
0.0...100.0 MVA
0.1 MVA
S>> delay time
0.0...60.0 s
5.0 s
P< [MW]
-1,000.0...1,000.0 MW
0.0 MW
P< hysteresis
0.0...100.0 MW
0.1 MW
P< delay time
0.0...60.0 s
5.0 s
P<< [MW]
-1,000.0...1,000.0 MW
10.0 MW
P<< hysteresis
0.0...100.0 MW
0.1 MW
P<< delay time
0.0...60.0 s
5.0 s
P> [MW]
-1,000.0...1,000.0 MW
0.0 MW
P> hysteresis
0.0...100.0 MW
0.1 MW
P> delay time
0.0...60.0 s
5.0 s
P>> [MW]
-1,000.0...1,000.0 MW
0.0 MW
P>> hysteresis
0.0...100.0 MW
0.1 MW
P>> delay time
0.0...60.0 s
5.0 s
Q< [kVar]
-100,000...100,000 kVar
0 kVar
Q< hysteresis
0...10,000 kVar
1,000 kVar
Q< delay time
0.0...60.0 s
5.0 s
Q<< [kVar]
-100,000...100,000 kVar
0 kVar