14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
307
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
Upper bandwidth delay time
0.0...60.0 s
0.0 s
Settings > Parameters > Switching interval monitoring (Total, Raise, Lower)
Maximum number of total tap-
change operations
1...100
10
Time period for total tap-change
operations
1...1,440 min
5 min
Message duration for total tap-
change operations
1...60 min
15 min
Behavior for total tap-change op-
erations
Off, Auto blocking, Auto-
>Manual
Off
Maximum number of raise opera-
tions
1...100
10
Time period of raise operations
1...1,440 min
5 min
Message duration for raise oper-
ations
1...60 min
15 min
Behavior for raise operations
Off, Auto blocking position
+, Auto->Manual
Off
Maximum number of lower opera-
tions
1...100
10
Time period for lower operations
1...1,440 min
5 min
Message duration for lower oper-
ations
1...60 min
15 min
Behavior for lower operations
Off, Auto blocking posi-
tion-, Auto->Manual
Off
Settings > Parameters > Move to the defined target tap position
Target-tap-position operation
-128...128
0
Settings > Parameters > Analog tap position capture (optional)
Upper tap position
-128..128
In accordance with order
Lower tap position
-128..128
In accordance with order
Settings > Parameters > IEC 61850 (optional)
IP address
2
0.0.0.0...255.255.255.255
192.168.10.254
Subnet mask
2
0.0.0.0...255.255.255.255
255.255.255.0
Gateway address
2
0.0.0.0...255.255.255.255
0.0.0.0
IED name
2
-
TAPCON
Device ID
2
-
TAPCON
Access point
-
-
Edition
Edition 1; Edition 2
Edition 1
Settings > Parameters > IEC 60870-5-101 (optional)
Serial interface
2
RS232, RS485
RS232
Baud rate
2
9.6...115.2 kilobaud
9.6 kilobaud