The following parameters are available for setting function monitoring:
▪ Function monitoring
▪ Hysteresis
▪ Delay time
Settings
Parameters
U bandwidt...ing
Name
Value
Function monitoring
Auto and Manual
Hysteresis
0.0 %
Delay time
15 min
Lower bandwidth hysteresis
0.1 %
Lower bandwidth delay time
2 s
Upper bandwidth hysteresis
0.1 %
Upper bandwidth delay time
2 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 146: Q bandwidth monitoring
1. Go to
Settings > Parameters > On-load tap-changer regulator > Q
bandwidth monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Also refer to
2
Function monitoring
You can use this parameter to activate function monitoring. You can select
the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and AVR
MANUAL operating modes
Table 76: Activate function monitoring
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.