14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
302
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
Time response T1
Linear, Integral
Linear
Activate delay time T2
On, Off
Off
Delay time T2
1.0...10.0 s
10.0 s
Regulation mode (optional)
2
Single-phase, Mean value
regulation
Single-phase
Control variable (optional)
L1/N or L1/L2, L2/N or L2/
L3, L3/N or L3/L1
L1/N or L1/L2
Settings > Parameters > Transformer data
Primary transformer voltage
2
0.057...1,000 kV
100 kV
Secondary transformer voltage
2
57 to 135 V
100 V
Primary transformer current
2
100...9,000 A
100 A
Secondary transformer current
2
0.2 A; 1 A; 5 A
1 A
Phase angle correction
-150...180°
0°
Voltage-transformer circuit
1-phase phase voltage, 3-
phase differential voltage,
3-phase phase voltage
1-phase phase voltage
Current-transformer circuit
1-phase phase current, 3-
phase total current, 3-
phase phase current
1-phase phase current
Settings > Parameters > Motor control
Switching pulse type
Time-controlled pulse,
Continuous pulse
Time-controlled pulse
Switching pulse time
0.1...10.0 s
1.5 s
Switching pulse pause
0.0...10.0 s
1.5 s
Motor runtime
0.0...30.0 s
6.0 s
Activate motor runtime monitoring Off, On
Off
Switching direction
Standard, Swapped
Standard
Activate switching direction moni-
toring
Off, On
Off
Settings > Parameters > Compensation
Compensation method
Off, R&X compensation, Z
compensation
Off
R&X compensation: Ohmic resis-
tance load
0.000...30.000 mΩ/m
0.000 mΩ/m
R&X compensation: Inductive re-
sistance load
0.000...30.000 mΩ/m
0.000 mΩ/m
R&X compensation: Length of
line
0...1,000.0 km
0.0 km
Z compensation: Voltage in-
crease
0.0...15.0%
0.0%
Z compensation limit value
0.0...15.0%
0.0%