8 Operation
Maschinenfabrik Reinhausen GmbH 2020
109
3587317/21 EN
TAPCON
®
Reference time
You can use this parameter to set which time is to be transmitted by the con-
trol system. The device uses this information for time synchronization
[
Section 8.5, Page 97]. You can select the following options:
Option
Description
Local
The control system transmits the local time.
Page 98]. Otherwise the device will use
an incorrect time.
UTC
The control system transmits the time as UTC. The de-
vice calculates the local time from UTC and the set time
zone [
Table 28: Reference time
8.8.4 Configuring IEC 60870-5-104 (optional)
If you want to use the IEC 60870-5-104 control system protocol, you must
set the following parameters. Also refer to the section Configuring the net-
work [
Settings
Parameters
IEC 60870-5-104
Name
Value
TCP port
2404
ASDU address
1
ASDU sequence optimization
None
Reference time
UTC
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
31.01.2020 13:05
Figure 84: IEC 60870-5-104
1. Go to
Settings > Parameters > System > IEC 60870-5-104
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
TCP port
You can use this parameter to set the TCP port.