Chapter Seven: Operation in Setup Mode
How To Set Up a Dual Channel Display
207
A. If the main display is correct, press the [
ENTER
] key.
B. If the main display is not correct, enter the correct switchpoint value, then press the
[
ENTER
] key.
The system responds by accepting the switchpoint value, and causing the right display to
blink.
6. Select a type of dual channel operation, (ct for continuous, dt for discontinuous, and OFF
to disable the function). The default is off (disabled).
A. If the right display is correct, press the [
ENTER
] key.
B. If the right display is not correct, use the arrow keys to scroll through the three
selections of dual channel operation.
The system responds by accepting the type of dual channel operation, and causing the
center display to blink.
7. Enter the channel number associated with the control sensor. The default is channel 1 for
both the upper and lower sensors.
A. If the center display is correct, press the [
ENTER
] key.
B. If the center display is not correct, enter the correct channel number (1 through 4),
then press the [
ENTER
] key.
The system responds by accepting the channel number entered.
Note
If you are setting the low switchpoint, the controlling sensor is the one
that controls at the lower range. If you are setting the high switchpoint,
the controlling sensor is the one that controls at the higher range.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com